Single Duct VAV Box

Features:

 

  • Ranges from 31 L/s to 1888 L/s
  • Pressure independent operation
  • Variable air or constant air volume application
  • Electronic or direct digital control
  • Factory calibrated to fit job requirement
  • External mounted DDC controller panel
  • Connection bead offers secured flex duct connection
  • Full range of accessories (coil, attenuator etc)

 

Structure:

 

  • 0.8 to 1.0mm G.I Structure

  • 25 mm and 48 kg/m3 fiberglass internal insulation, facing with marglass and perforated metal sheet protection. Meets requirement of BS476 part 6 and HKFSD regulation

  • Blade type damper formed by two layers of heavy gauge galvanized steel with sandwich peripheral gasket

  • Plated damper shaft is mounted in self-lubricated bearings

  • UL 94 type pneumatic tubing

  • Discharge with completed J2 flange and meet DW 144 requirement

  • Special liner and insulation available

 

VAV Model l / s   c f m
Minimum Maximum   Minimum Maximum
VAV - 5000 - 06 31 212   66 450
VAV - 5000 - 08 62 378   132 800
VAV - 5000 - 10 104 637   221 1350
VAV - 5000 - 12 143 991   304 2100
VAV - 5000 - 14 207 1416   439 3000
VAV - 5000 - 16 268 1888   568 4000
Internal Parts

12 point cross flow sensor

Eaton Symflex "1219 FR" UL 94 type pneumatic tubing

fiberglass internal insulation, facing with marglass and perforated metal sheet protection